Products summary
1. Distribution intelligent monitoring terminal has all-around 3-phase power
Measurement,128*64LCD display ,harmonic analysis, over limit control ,the quantity of switch output /input, moving reactive compensation ,electrical energy computation ,event record ,communication as one.
2.original appearance design, it has two ways terminal that choi hanging and embedded .It installation on panel or cabinet. When you think about the installation methods , you should according to the routing principle of easy to installation ,look and collection ,in favor of signal and power.
3.be the same with public variable area ,industrial enterprises ,JP cabinet ,phasetransition , digital auto motor distribution and intelligent reactive compensation controller .
4.The software arithmetic of developed AC sample , precise and reliable combing the hardware circuit, embedded with lead can turn type panels, apply to constantly up granding electric field ,reliable emc design and make to a kind of distribution intelligent monitoring terminal convenience.
5.Distribution intelligent monitoring terminal support RS-232/485gorge line one and RS-485gorge line two .The gorge line two is data resent gorge line(just used in embedded) and it main support more function resent data of electric electrical degree .
The communication method of gorge line one support UTP ,Coaxial Cable ,Data Radio and GPRS ,otherwise it also exploit light MODBUS and optical fiber to communicate .It finished a kind of the monitor function of the distribution terminal ways.
Technology parameter:
Environment requirement :
High above sea level:≤2500m
Working temperature:-20°C~+60°C Store temperature : -25°C~+70°C
Surrounding hasn’t medium of corrosive gas, electric dust , inflammable and explosive. There are hasn’t knock cold and sleet corrode in installation place.
Working power : 220V±20% (A type) 85V~265V(B type )
Weight :1.5Kg
Measuring signal : split phase
Measuring method: AC sampling
Measuring voltage :59v~280v Measuring current :0~5 A
Measuring power factory : lag0.200~ a head 0.200
Measuring harmonic :digital display
Measuring active power :0~999.9Kw(split phase)
Measuring reactive power :0~999.9Kvar(split phase)
Measuring active electric degree :0~999999.99Kwh
Measuring reactive electric degree: 0~999999.99Kvarh
Input/output signal:
Reactive compensation output:12v 30mA/branch
The quantity of on/off output:12v 30mA/branch♣(need out delay)
The quantity of on/off input :main point output (needn’t out delay) ♣
Temperature quantity input:PT100
Alarm output :250v 5A DELAY MAIN POINT
Communication interface data:
RS-485
Communication interface 1: using in remote terminal data select
Method:RS-485/RS-232(to select use front panel bouncing pin)
Brand rate :1200,2400,4800,9600,38400
Data post:8 data post
Parity bit: can setting
Stop spot:1 stop spot
Communication interface 2: using on terminal and other intelligent equipment interface ♣Method : RS-485
Brand rate:1200,2400,4800,9600,38400
Data post:8 data post
Parity bit: can setting
Stop spot:1 stop spot
Measuring accuracy:
Voltage : ±0.5% Power : ±1.0%
Current ±0.5% Frequency: ±0.5%
Power factory: ±1.0% Electric quantity: ±1.0%
Above data get for after 10min and within 1 year current .
Setting data:
Voltage upper limit: 240v~275v Step-length:5v
Voltage lower limit: 175v~200v Step-length:5v
Goal power factory : 0.90~1.00 Step-length:0.01
Current transformer ratio : 1~1200
Capacitor switching delay time :20mS~300S
Harmonic voltage setting data: 5%~50% Step-length:0.5%
Tlock:0.5~1.2 Step-length:0.1
Zero sequence current :5%~50% Step-length:5%
Attention: “♣” is only Embedded structure product has the function .