JKWC+Lcd reactive compensation controller
1. Safety Tips
The installation, connecting or debugging of the production should be done following the instruction of the manual; at the same time, pay attention to the wiring diagram and the sign of Terminal point at the rare of the controller.
When the shell of controller was broken or the monitor not working , stop using it and connect with supplier.
The installation should strictly follow the operating instruction in the respect of the standard of safety. Follow the correct way of wire connecting and electric wire size to guarantee the safety, reliability of operation, and the accuracy of measure.
When connecting with electricity, both side of CT will generate High-voltage surge which is dangerous to our life. Be careful when operating, strictly follow the operating instruction of safety utilization of electric power.
Only trained work allowed to use according the instruction and safety regulation.
2. Product Introduction
2.1 Full Digitalization designed, AC Sampling, the human-machine interface is using a large-screen LCD liquid-crystal display .
2.2 Following the concept of people oriented, modularization installed with streamline case design .
2.3 Real-time display the parameters of power factor ,voltage, electrical current, active power , reactive power , the rate of voltage and current distortion , average value of frequency and the condition of capacitance.
2.4 Set the Chinese parameter tips ,digital input .
2.5 The capacitor switching control program can support equal volume/coding (1:2:2 1:2:3 1:2:4:8……..) and the fuzzy control mode of switching .
2.6 It has a manual /automatic compensation two kinds of control way .
2.7 Physical quantity sampling is reactive power has the function of measuring Harmonic and protection.
2.7it has temperature measurement and control output functions.
3. Technical Parameter
Environmental requirement
Height:≤2500m
Operating temperature: -20°C~+60°C
Storage temperature: -25°C~+70°C
Operating in the environment of no corrosive gas, no conductive dust and no explosive and flammable medium. The Installation site should be no violent vibration and erosion of snow and rain
Measured data
Measuring voltage:100V~500V
Measuring current:0~6000A
Power factor measurement:Lag 0.200~ahead 0.200
Measuring voltage: 400V
Measuring cuttent:0~6000A
Sensitivity :120mA(twice)
Power factor measurement:lag 0.200 ~ahead 0.200
Measurement temperature : 20°C~80°C
Total harmonic distortion: 0.0~100.0%
Input/Output signal
Sampling voltage: line voltage
Current Sampling: bus-bar current transformer twice 0~5A
Control output: The electric relay stem node 5A/250V Resistive (static)
12V 300mV/ branch road ( dynamic)
Over-temperature control output : 5A 250V The electric relay stem node
Sampling voltage isn't the same as the current sampling
Display performance
The LCD Digital data display refresh cycle≤1s
Measuring accuracy
Voltage ±0.5%
Electric current ±0.5%
Power factor ±1.0%
The statistics above is getting by 10 minutes' preheating of controller and calibration within one year .
Setting data
Rated transformation ratio: 1~1200(ratio)
Delay Time: 5s~100s
Target COSφ:lag 0.80~ahead -.80 step length 0.01
Overvoltage setting:400V~480V step length 2V
On and off limit:0.5~1.2(setting value is on limit value) step length 0.1
Off limit = 1.2 - current setting
Harmonic protection: Hv: 0.0%~50.0%
Output group count: 2~12
Capacitance preset: 0~999Kvar/group
Reliability:
Mean Time Between Failures(MTBF) > 25000 hours
JKWC+Lcd reactive compensation controller